Overview

The automatic evacuation broadcasting function to assist fast and safe evacuations from fire. It uses the optimized scenario which is pre-set depending on fire locations to minimize casualties by providing the first priority zone to be evacuated, evacuation directions for each zone, and ways to evacuate from the initial fire location based on time interval.

Feature

- AUTOMATIC EM SCENARIO BROADCAST

• The automatic evacuation broadcasting function to assist fast and safe evacuations from fire. It uses the

    optimized scenario which is pre-set depending on fire locations to minimize casualties by providing the first

    priority zone to be evacuated, evacuation directions for each zone, and ways to evacuate from the initial fire

    location based on time interval.

• As a critical component in the emergency system, it can prevent delayed responses due to possible lack of an

    operator or through unskilled operation.


- BYPASS FUNCTION

  Allows for conversion to basic evacuation broadcast or operator control.


- PC BACKUP

  Scenario data written to PC is saved in built-in memory; no problems will occur as a result of a PC failure.


- 99 MESSAGES CAPACITY

  PV-6232 (VOICE FILE) enables use of 99 messages.


- SYSTEM EXPANSION

  Through RS-485 communication, it can be expanded to maximum 10 systems.

Specification

ER-6116
Channel 16CH
Communications Protocol LINK IN/OUT RS-485 (Maximum 1km/3,280 feet)
VOICE FILE RS-232 (Maximum 12m/40 feet)
Fire Sensor Dry Contact
Operating Temperature -10°C ~ +40°C / 14°F ~ 104°F 
Power Source DC 24V, 100mA
Weight (Set) 2.8kg/6.2lbs
Dimensions (Set) 482(W)x44(H)x280(D)mm/19(W)x1.7(H)x11(D)in