applications

ECS-6216S

Overview

The ECS-6216S output slave unit allow the addition of 16 output zones to the single bus system 6000. Up to 9 units can be added to the ECS-6216P, giving the system up to 160 output zone capacity. Each unit also offer 16CH GPI sensor input for messaging, event and scenario triggering.

Feature

- INTEGRATED SYSTEM

  System consists of EMERGENCY SWITCHER, MATRIX, RELAY GROUP, SPEAKER SELECTOR, and 

  TERMINAL BOARD functions.


- BROADCAST CONTROL DEPENDING ON PRIORITIES

  It controls the priority broadcasting by connecting to emergency panel (EP-6216) and remote MIC (RM-6024).

  It switches to remote or emergency broadcasting due to priorities of emergency signals or outside remote signals

  (remote MIC broadcasting signals) even if during general broadcasting.


- AUTOMATIC FIRE DETECTING FUNCTION

  With 16-channels corresponding to fire contact point signals, fire alarm broadcasting will be
  transmitted 
automatically.


- MANUAL CONTROL OF EMERGENCY AND GENERAL BROADCASTS

   It can broadcast to desired channels by manually selecting emergency or general broadcasting.


- DISPLAY BROADCASTING STATUS

   It displays the priority and broadcasting status on LED, so user can verify the broadcasting status
   without any 
effort.


- MEMORY/SAVE FUNCTION

  Fire/RM Macro information will be saved in internal PC memory allowing for normal
  operation in event of PC 
error.


- CHANNEL EXPANSION AND RS-485 COMMUNICATION INTERFACE

  Long distance transmission is available and system can be expanded to 160 Zones by utilizing ECS-6216S.


- INSTALLATION TIME AND SPACE

  Since it is an integrated system, it is easy to install and can save installation labor, time and space.

 - Automatic Check

   Check the status of amp connected to each channel automatically according to the time-set.


 - Display Amp Status

   Display the status of amp connected to each channel by LED


 - Automatic Change

   Channel which fault occurs when checking out the amp will be switched to spare amp automatically.


 - Check Time setup

   You can set up 5 different time intervals for automatic self check.

Specification

ECS-6216P/S
Priority Emergency>Timer>Remote 1>Remote 2>Main
Channel 16CH
Communications Protocol LINK IN/OUT RS-485 (Maximum: 1km/3,280 feet)
RM INPUT (RM1, 2) RS-422 (Maximum: 1km/3,280 feet)
SOURCE RS-232 (Maximum: 12m/40 feet)
Fire Sensor Dry Contact
Operating Temperature -10°C ~ +40°C/14°F~104°F 
Power Source DC 24V, 900mA
Weight (Set) 4.3kg/9.5lbs
Dimensions (Set) 482(W)x88(H)x280(D)mm/19(W)x3.5(H)x11(D)in